The following line post insulators comply with the ANSI Standard. The glaze colors of the insulators are brown or light gray. The dimension of neck for 57-1, 57-2, 57-3 is in accordance with "F". The dimension of neck for 57-4, 57-5 is in accordance with "N".
Dimensions:
Diameter (D): 7 1/2 Inches (190mm)
Height (H): 20 Inches (508mm)
Leakage Distance: 45 Inches (1145mm)
Dry Arcing Distance: 17 1/4 Inches (438mm)
Mechanical Values:
Cantilever Strength: 2,800Pounds (12.5kN)
Cantilever Strength Routine Test: 1,000Pounds (5kN)
Electrical Values:
Typical Application Voltage: 66kV
Low Frequency Dry Flashover Voltage: 175kV
Low Frequency Wet Flashover Voltage: 150kV
Critical Impulse Flashover Voltage, Positive: 290kV
Critical Impulse Flashover Voltage, Negative: 380kV
Radio Influence Voltage Data:
Test Voltage RMS to Ground: 44kV
Maximum RIV at 1000 kHz: 200μV
Packing and Shipping Data:
Net Weight, Approximate: 18.0kg