The following line post insulators comply with the ANSI Standard. The glaze colors of the insulators are brown or light gray.
Dimensions:
Diameter (D): 6 11/16 Inches (170mm)
Height (H): 15 Inches (381mm)
Leakage Distance: 27 1/2 Inches (699mm)
Dry Arcing Distance: 14 Inches (356mm)
Mechanical Values:
Cantilever Strength: 2,800Pounds (12.5kN)
Cantilever Strength Routine Test: 1,000Pounds (5kN)
Electrical Values:
Typical Application Voltage: 30kV
Low Frequency Dry Flashover Voltage: 120kV
Low Frequency Wet Flashover Voltage: 85kV
Critical Impulse Flashover Voltage, Positive: 210kV
Critical Impulse Flashover Voltage, Negative: 230kV
Radio Influence Voltage Data:
Test Voltage RMS to Ground: 30kV
Maximum RIV at 1000 kHz: 200μV
Packing and Shipping Data:
Net Weight, Approximate: 12.8kg